Currently Viewing Product 2 of 12
AD-99-0465: TP-015L ProSens 1 (High Sensitivity)
Model: AD-99-0465
QTY :
TP-015L ProSens 1 (High Sensitivity c/w 0.015% Detector)
Applications
The robust TITANUS PRO·SENS® offers a comprehensive product range complete with accessories approved to EN 54-20. This allows the device to be used in areas where other smoke detectors and air sampling smoke detection systems have long reached
their limits. These include:
- IT areas and clean rooms
- General warehouses, high bay storage areas and
- cold storage areas
- Production and assembly lines
- Wind farms
- Libraries, museums and archives
- Hospitals, hotel rooms and saunas
- Recycling areas
- Rail vehicles and tunnels
Basic equipment | TITANUS PRO-SENS® (/net) | TITANUS PRO·SENS® 2 (/net) |
---|---|---|
Number of Detector Modules | 1 | 2 |
max. number of sampling holes | 32 | 64 |
max. pipe length (with max. number of sampling holes) | 300 m | 560 m |
Monitored area per sampling hole | Corresponds to one point-type smoke detector in accordance with VDE 0833-2 | |
Monitoring of pipe systems for breakage and obstruction | Optional adjustment for individual hole monitoring** | |
Double-knock detection | Possible using detector box | Yes (separate room and equipment protection) |
Sensitivity detection unit DM-Tx-01 - (Sampling holes in accordance with EN 54-20: - Classes A max. 2 x 32, B max. 2 x 32 and C max. 2 x 32) | Info-alarm: 0.005 % LT/m* | |
Pre-alarm: 0.01 % LT/m* | ||
Main alarm: 0.015 % LT/m | ||
Sensitivity detection unit DM-Tx-10 - (Sampling holes in accordance with EN 54-20: - Class A max. 2 x 9, Class B max. 2 x 32, Class C max. 2x32) | Info-alarm: 0.03 % LT/m* | |
Pre-alarm: 0.07 % LT/m* | ||
Main alarm: 0.01 % LT/m | ||
Sensitivity detection unit DM-Tx-50 - (Sampling holes in accordance with EN 54-20: - Class A max. 2 x 4, Class B max. 2 x 12, Class C max. 2x32) | Info-alarm: 0.17 % LT/m* | |
Pre-alarm: 0.3 % LT/m* | ||
Main alarm: 0.5 % LT/m | ||
Alarms (Volt free C/O) | Up to 3 alarms per detector module (Info, Pre and main alarm)* | |
Fault alarms | Common Alarm (1 x volt free contact per module, NC or NO) | |
Alarm and fault relay power rating | 1 A, 30 V DC, max. 24 W | |
Clamped connections | Max. 1.5 mm² | |
Displays on device | ||
- Main alarm (TP-1/a, TP-3, TP-4, TP-5) | 1 red alarm display for each* | |
- Pre-alarm (TP-4, TP-5) | 1 red alarm display for each* | |
- Info-alarm (TP-5) | 1 red alarm display for each* | |
- Fault | Yellow common fault | |
- Operation | Green operation display | |
Operating voltage | 24 V DC (14 - 30 V DC) | |
Max. quiescent current (at 24 V DC) | 200 (210) mA* | 220 (240) mA* |
Max. alarm current (at 24 V DC) | 210 (220) mA* | 240 (250)mA* |
Starting current limted to | 300 (390) mA* | 320 (400) mA* |
SL Version | ||
Max quiescent current (at 24vdc)*** | 150 (140) mA* | 180 (170) mA* |
Max current in alarm (at 24vdc)*** | 160 (150) mA* | 190 (180) mA* |
Staring current limited to | 300 (230) mA* | 330 (260) mA* |
Noise Level (with sound damper) | from 23 dB (A) | |
Dimensions (W x H x D) | 200 x 292 x 113 | |
Weight | 1460 g | 1560 g |
Protection category | IP20 (optional IP52) | |
Temperature range | -20 °C to + 60 °C | |
Cold storage option (No SL ver) | -40 °C to + 60 °C | |
Humidity (permanent) | 10 % to 95 % relative humidity | |
Event log | Built-in, additional external data storage possible | |
Connection of external alarm notifications | Parallel display optional | |
Network capability | optional ethernet network version**** | |
Approved in accordance with EN 54-20, Classes A, B, C: | ||
- VdS-No. | G 206004 | |
- BPRI-No. | 0786-CPD-20685 | |
* depending on device type ** depending on project design ***At std 6.9 V fan **** Version TITANUS PRO-SENS /net |
Shipping Weight: 1500gms