Currently Viewing Product 9 of 13
CFP762: Relay Output Card
£44.63
CFP Relay Output Card, provides reset, fault, aux & remote relay outputs.
This Relay Output Card is designed to mount inside the CFP Fire Alarm Panel. When connected, it provides the following isolated (voltage free) relay outputs which are directly controlled from the Panel.
Reset Changes over during the Panel’s reset cycle.
Stays in this state for at least one second after all other Outputs have normalised.
Typically used for resetting Fire System devices such as beam detectors.
Fault Changes over for any fault condition (unless the User has disabled the Panel’s Fault Output).
This output is failsafe in that the relay is energised when there is no fault. If the power is completely removed from the Panel then the relay will change over to produce a fault signal.
Aux Changes over when there is an Alarm Condition and any Delay has expired or been overridden (unless the User has disabled the Panel’s Aux. Output). Typically used for controlling Fire
System devices such as door closers, ventilation shut down, etc.
Rem Changes over when there is an Alarm Condition and any Delay has expired or been overridden (unless the User has disabled the Panel’s Remote Output). Typically used for connection to Remote signalling equipment.
For more information, please visit this product's webpage.