Currently Viewing Product 2 of 17
FIRERAY 100R Reflective Infrared Beam Detector with Prism - 100m
Technical Specification |
|
Operating Range F50RV / RU: | 5 to 50 Metres |
Operating Range F100RV / RU: | 50 to 100 Metres |
Operating Voltage Range: | 10.2V DC to 30Vdc |
Quiescent Current: | <4mA @ 24Vdc |
Alarm Current: | <15mA |
Power Down Reset Time: | 5 seconds |
Fire Relay Contacts: | Normally Open, VFCO 2A @ 30 Volts DC, resistive |
Fault Relay Contacts: | Normally Closed, VFCO 2A @ 30 Volts DC, resistive |
Operating Temperature | -20°C to +55°C (non-condensing) EN54 Applications -10°C to +55°C (non-condensing) |
Fire Alarm Thresholds: | 1.25dB (25%), 1.87dB (35%), 3.00dB (50%) |
Optical Wavelength | 880nm |
Detector Dimensions: | Width 126mm, Height 210mm, Depth 120mm |
Prism Dimensions: | Width 100mm, Height 100mm, Depth 9.5mm |
Weight: | 0.67 kg |
LED Indications: | Red LED: Indicates FIRE Continuous Amber LED: Indicates FAULT Flashing Amber LED: Once every 10 seconds indicates normal operating mode (RV Models only) Flashing Amber LED: Once every 2 seconds indicates the compensation function has reached its limit |
Conditions: | Alarm Condition: Indicated by fire relay closing Fault Condition: Indicated by fault relay opening Alarm may be latching or non-latching (default) |
IP Rating: | IP50 |
Relative Humidity: | RH 0% to 93%, (non-condensing) |
Approvals/Certification: | Designed, manufactured and certified to EN54-12: 2002, Use 25% and 35% (default) thresholds. The 50% threshold is recommended for hostile and extreme environments. 0786-CPD-20045 |
CPD Reference: UL File: | S3417 |
Parts List: | 1 x Detector Head Assembly, 1 x prism (50R) or |
| 4 x prisms (100R), 1 x Test Filter, 1 x Cable Interface |
Housing Construction: | Flame Retardant ABS, Finish: Grey / Black |