Ei184 Heat Alarm. Interconnectable. Built-in 1A Relay
Heat Alarm. 12V-24V with Alkaline Battery Back-up. Interconnectable. Built-in 1A Relay
The Ei184 Heat Alarm runs on 12V to 24V variable DC power, and has a 9V Alkaline battery back-up. The alarm gives a fire warning when adequate heat enters the alarm.
The alarm is supplied with an easi-fit base that allows quick and simple installation of the smoke alarm head. The easi-fit base automatically connects both the mains power and battery as the alarm slides on.
The Ei184 Heat Alarm has a pair of built-in Volt free relay contacts (i.e. can be used to switch into a burglar panel).
The alarm has other advanced features such as built-in circuitry to aid suppression of voltage transients and RF interference to further reduce the chances of false alarms under such conditions.
Features
- 12-24V DC Powered
- 9V Alkaline battery back-up
- Fixed temperature fast response thermistor type sensor, triggers at 58°C (Best for large flaming fires)
- Volt-free Relay contacts built in
- easi-fit Base
- Advanced supression and calibration technology
- Interconnect up to 12 alarms
- Built-in Test/Hush button
- Piezoelectric horn
- Battery removed indicator
- Low battery audible warning
- Kitemarked to BS 5446 Pt.2:2003
- 5 Year Guarantee
Specification
Sensor Type: Thermistor
Supply Voltage: 10.5 to 30 V DC
Battery Back-up: 9V Alkaline battery
Relay Contacts: Volt free, Common/NO/NC
Horn: Piezoelectric
Sound Level: 85 dB(A) at 3 meters
Temperature: Operating - 0°C to 40°C / Storage - 0°C to 35°C (in a dry area)
Humidity Range: 0% to 90% Relative Humidity
Button Test: Simulates the effect of smoke and checks chamber, electronics and horn
Self Test: Smoke chamber and battery is automatically tested every 40 seconds
Indicator LED’s: Green - Power On / Red - Alarm and Fault event
Plastic material: UL94HB flame retardant
Dimensions: Product - 145mm x 65mm
Weight: 363g (including packaging)
Fixing: Screw fixings supplied
Warranty: 5 year (limited) warranty
Approvals: Kitemarked to 83678 / BS 5446-2:2003